The four-pin plug of the interface cable must be inserted into the corresponding socket in the
device. The USB plug must be inserted into a free USB port on the PC.
More information on configuring via the PC configuration software can be found in the
Operating Instructions.
No power should be supplied via the bus if configuring the PROFIBUS PA indicator with
the DTM via the CDI interface!
To ensure a connection to the device can be established, operation must be set to
"Remote" at the DIP switches. Furthermore write protection, which can be enabled and
disabled via the DIP switches, must be disabled so that the parameters of the field
indicator can be modified via the DTM.
The DIP switches are described in the "Operation" section →  43.
6.4
Hardware settings
Hardware write protection can be enabled and disabled via DIP switches inside the field
indicator. When write protection is active, parameters cannot be modified.
The current write protection status is displayed in the WRITE_LOCK parameter.
ESD - Electrostatic Discharge
Protect the terminals from electrostatic discharge. Failure to observe this may result in destruction or
malfunction of parts of the electronics.
A0012751
To set the DIP switches, proceed as follows:
1.
Open the housing cover.
2.
Configure the DIP switches. Switch to ON = function enabled, switch to OFF = function
disabled.
3.
Close the housing cover and secure it.
1
 13
Hardware configuration of the field indicator
Endress+Hauser
Operating the field indicator
ON
OFF
A0021499
43