5. Installation
The tasks described in this section may only be
carried out by a qualified electrician.
5.1
Choice of location
The device is solely intended for fixed floor mounting. A
suitable location meets the following requirements:
„ Technical data and mains data are the same.
Î "4. Technical data"
„ Permitted environmental conditions are observed.
„ The minimum distances are respected.
5.1.1
Permitted environmental conditions
T
T
DANGER
Danger of injury and fire
If the device is operated in potentially explosive
atmospheres (explosive area), explosive substances may
ignite due to sparking of components of the device.
f Do not use the device in potentially-explosive
atmospheres (e.g. at gas filling stations).
T
T
ATTENTION
Device damage due to unsuitable ambient conditions
An unsuitable choice of location may cause damage to the
device. Please note the following points when choosing a
location:
f Do not place the device in areas at risk of flooding.
f Protect the device from direct water jet.
MENNEKES recommends protecting the device
with on-site curbs or bollards.
Permitted environmental conditions
Ambient temperature
Average temperature
over 24 hours
Relative humidity
5.1.2 Minimum distances
T
T
ATTENTION
Damage to the device due to insufficient ventilation.
Insufficient ventilation can lead to overheating and thus to
damages to the device.
f Observe the specified minimum distances to other
objects (e.g. walls).
Please observe the specified minimum distances also for
barrier-free access during operation and maintenance and
repair work.
2 5
0
8 0 0
Fig.: 5. Minimum distances (mm)
-25 to +40 °C
< 35 °C
max. 95 % (non-condensing)
8 0 0
1 2
5 0
EN