Herunterladen Inhalt Inhalt Diese Seite drucken

Sulzer ABS CA 441 Installationshandbuch Seite 47

Vorschau ausblenden Andere Handbücher für ABS CA 441:
Inhaltsverzeichnis
Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 16
1.5.3 CA 443
Book_81307110_CA44x.indb 47
Book_81307110_CA44x.indb 47
Dit product dient om het stroomverbruik, de faseafwijking en de spannings ingang voor een pomp of
een compleet station te meten.
If pump is operated from a frequency converter, special precautions are required.
The high electric noise level can distort electrical readings, especially phase timing readings are
sensitive to switch transients from frequency converter.
Turn off all phase related alarms and dry run detection in PC 441 and ensure PC 441 firmware ver-
sion is V.1.42 or later
Normal current transformers operate from 45-60 Hz and must be placed on mains line input to
frequency converter.
Use only mains phase (voltage) missing alarm for pump protection (blocking).
To avoid conducted electrical noise in cabinet, follow best practices and manufacturer EMC compli-
ance recommendation when installing frequency converters. Use shielded cables. Ensure mains
and motor cables are separated from signal cables in cabinet.
General precautions:
If CA 443 for P1 also is used for mains monitoring, L1, L2 and L3 voltage inputs must be connected
before pump circuit breaker
Tabel 9.
CA 443 gegevens
Ingang
Spanning
30 - 300 V ac ± 5.0 V ac
0 - 5 A ± 0.1 A ac fasewissel
Stroom
0 - 90 gr ± 1.5 gr
Tabel 10. Verbindingen onderzijde
Dir.
#
Signal
Sensor 1
6
Sensor 2
7
Sensor 3
8
GND
9
a Sensor 4
10
b GND
11
a Sensor 5
12
b GND
13
a Sensor 6
14
b GND
15
Tabel 11. CA 443 LED indicators from PC 441 firmware 1.42
LED
Indication
Mains monitor (0 or 1)
1
Phase 1
Voltage missing
2
Phase 2
Voltage missing
3
Phase 3
Voltage missing
4
Warning
Alarm wrong phase order
Alarm phase missing
Pending high voltage
Pending low voltage
Pending unbalanced voltage
Pending high freq.
Pending low freq.
Bereik
Commentaar
Gebruik een spanningsom-
vormer bij hogere voltages
Gebruik altijd een transforma-
tor
Description
AC spanningsingang L1
AC spanningsingang L2
AC spanningsingang L3
Spanning referentie ingang
Stroom transformator ingang 1
Stroom transformator ingang 2
Stroom transformator ingang 3
Pump monitor (1-4)
Voltage missing
Voltage missing
Voltage missing
Alarm phase current missing
47