Herunterladen Inhalt Inhalt Diese Seite drucken

EBARA Ego 2 slim Installations- Und Bedienungsanleitung Seite 34

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 38
ETHERNET
Only available in Module C, installed in variant Ego 2 slim and Module C.
The pump has a built in web server which allows you to access your pump directly via an existing Ethernet
connection. The default address for access to the pump is 192.168.0.245/
The web server uses HTML pages to set and view:
Regulation mode settings
Regulation parameters (power, RPM, head, flow)
Relay settings
External control inputs settings
Current and previews error
Pump statistics (power consumption, run time and other)
MODBUS
Only available in Module C, installed in variant Ego 2 slim and Module C.
Pump has built in Modbus client, through which we can access pump information using the RS 485 standard.
Modbus allows us to set and view:
Regulation mode settings,
Regulation parameters (power, RPM, head, flow),
Relay settings,
External control inputs settings,
Current and previews error,
Pump statistics (power consumption, run time and other).
RESETTING PUMP TO FACTORY SETTINGS
For resetting the pump to factory settings all three buttons must be held for 5 seconds. This way the pump will
set itself to automatic mode, delete previous height and power settings and unlock setting pump operation (if
locked).
Resetting of communications module needs following steps:
1. Disconnecting power from pump,
2. Set the 10-step switch to number 9
3. Turning the pump on and off again,
4. Setting the 10-step switch to number 1,
5. Turning the pump on.
Communications module should now be set to factory settings.
5
This also sets up the right twin pump.
5
(or 8 for left twin pump),
34

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis