• "E Housing, Series COMBIVERT Cat. No. 12, 13, 14, 15 or 16 followed by F5, followed
by B or C, followed by 0, 1, 2 or 3, A, B, C or D, followed by E-, followed by four suffixes
E Housing, Series COMBIVERT Cat. No. 12, 13, 14, 15 or 16 followed by F6, followed by
B or C, followed by 0, 1, 2 or 3, A, B, C or D, followed by E-, followed by three suffixes and
followed by 4 or E or J.
Motor Overtemperature Protection:
above drive models are not provided with load and speed sensitive overload protection
and thermal memory retention up on shutdown or loss of power (for details see NEC, ar-
ticle 430.126(A)(1)".
For 240 V Models:
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 10000 rms Symmetrical
Amperes, 240 Volts Maximum, when Protected by Fuses, see Instruction Manual for speci-
fied fuse details and alternate Branch Circuit Protection details."
For 480 V Models:
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 10000 rms Symmetrical
Amperes, 480 Volts Maximum, when Protected by Fuses, see Instruction Manual for speci-
fied fuse details and alternate Branch Circuit Protection details."
For all Models:
Branch Circuit Protection:
Inverter
Input
model
Voltage
F5/F6
12
480 / 3ph
13
240 / 3ph
13
480 / 3ph
14
240 / 3ph
14
480 / 3ph
15
480 / 3ph
16
480 / 3ph
(#) manufactured by Siba Sicherungen-Bau GmbH
The voltage rating of the Class rated fuses shall be at least equal to the voltage rating of the
Drives.
input fusing
Fuse class RK5 or J or CC
(V)
UL 248
[ A ]
25
40
25
50
30
40
50
Anhang
Semiconductor fuses
Cat. No.
(#)
50 140 06 25
50 140 06 80
50 140 06 40
50 140 06 100
50 140 06 50
50 140 06 80
50 140 06 100