9.2. Main overview (home)

In the main overview (home), all important operating information is represented at a glance.

Meaning of the symbols

Air humidification "Off"
(red)
Air humidification "Standby"
(yellow)
Air humidification "On"
(green)
Air humidification enabled
Externally: Digital input or Modbus
Internally: Volume flow
Air humidification not enabled
Externally: Digital input not closed or Modbus
enable inactive
Internally: Volume flow not detected
Airflow available
(green)
Airflow not available
(red)
Message active
KWL
Hygrobox KWL HBX EH/WW
®
25.06.2021 10:14
50 % RH
50 % RH
22,0 °C
22,5 °C
The air humidification unit is inhibited manually and can be enabled by
pressing this button.
The air humidification unit is in the Standby mode. If the relative humidity
set is lower by more than 5 %, the air humidification unit switches on, if it is
enabled.
The KWL HBX is in the operating mode, i.e. there is a unit enable and a
system deviation. TheKWL HBX carries out regulation to the air humidity set
and the air temperature set. If the measured air humidity is in a range of
+/- 2 % of the air humidity set, and the water valve merely opens sporadi-
cally within 12 hours, the KWL HBXchanges to standby operation.
Depending on the configuration, a unit enable can either only be effected
via an airflow detection or additionally via a digital enabling contact or
enable via Modbus.
The flow sensor integrated at the outlet of the KWL HBX automatically
detects a present air volume flow. This is always a prerequisite for a unit
enable.
This message is shown when faults or warnings are pending. Touching the
symbol will lead you to the message overview.
With this parameter, the desired air humidity at the KWL HBX outlet with a
relative humidity between 40 % and 60 % is set.
A factory default value of 50 % RH is preset.
With this parameter, the desired air temperature at the KWL HBX outlet is
set between 15 °C and 25 °C.
A factory default value of 21 °C is preset.