12. Mounting

12.1. Prerequisites for the unit installation

The national and local regulations must be heeded when installing and setting up the unit. The unit may only be installed in compli-
ance with national installation regulations.
The unit may only be installed in frost-free and dry rooms. The temperature at the place of installation must be between +5 °C min.
and +35 °C max. The unit is intended for horizontal mounting. It must be mounted on a massive, load-bearing wall with a maximum
permissible deviation of +/- 1° from the horizontal position. The net operating weight of the humidification unit must be taken into
consideration for the suspension. The unit must not be exposed to vibration of any kind.
The air humidification unit may only be installed in rooms where a water drain is available.
In the place of installation, safety measures are to be provided for, automatically and reliably shutting off the water supply to
the air humidification unit in the event of an uncontrolled water discharge (water stop).
Air ducts of the ventilation system that are not installed in heated areas must be designed with suitable thermal insulation,
in order to prevent potential condensation when the temperature falls below the dew point temperature.
The place of installation for the air humidification unit must be readily accessible for maintenance and repair work. The
specified maintenance clearances with regard to the unit must be strictly observed.
The warranty will be void for potential damage due to non-compliance with this note!

12.2. Minimum clearances to be observed

Minimum clearances with regard to the unit must be adhered to for the assembly, in order to enable the maintenance work required.
I
KWL
Hygrobox KWL HBX EH/WW
®
Maintenance clearances for the KWL HBX 250:
Wartungsabstände LBE250:
A.
.. 200 mm at the top
A... 200mm Oben
B.
.. 250 mm at the bottom
B... 250mm Unten
C.
.. 360 mm front lid  front
C... 360mm Frontklappe vorne
D.
.. 330 mm front lid  - bottom
D... 330mm Frontklappe unten
E.
.. 110 mm UV tube maintenance front
E... 110mm UV-Röhre Wartung Front
F.
.. 170 mm UV tube maintenance length
F... 170mm UV-Röhre Wartung Länge
G.
.. 80 mm UV tube maintenance floor
G... 80mm UV-Röhre Wartung Boden
H.
.. 65 mm UV tube maintenance height
H... 65mm UV-Röhre Wartung Höhe
I.
.. 350 mm UV tube maintenance extension
I... 350mm UV-Röhre Wartung Auszug
Maintenance clearances for the KWL HBX 500:
Wartungsabstände LBE500:
A.
.. 250 mm at the top
A... 250mm Oben
B.
.. 250 mm at the bottom
B... 250mm Unten
C.
.. 530 mm front lid  front
C... 530mm Frontklappe vorne
D.
.. 470 mm front lid  - bottom
D... 470mm Frontklappe unten
E.
.. 170 mm UV tube maintenance front
E... 170mm UV-Röhre Wartung Front
F.
.. 170 mm UV tube maintenance length
F... 170mm UV-Röhre Wartung Länge
G.
.. 80 mm UV tube maintenance floor
G... 80mm UV-Röhre Wartung Boden
H.
.. 65 mm UV tube maintenance height
H... 65mm UV-Röhre Wartung Höhe
I.
.. 350 mm UV tube maintenance extension
I... 350mm UV-Röhre Wartung Auszug
28
C
F
E