Herunterladen Inhalt Inhalt Diese Seite drucken

GF PF220 V2 Betriebsanleitung Seite 48

Ultraschall-durchflussmessgerät
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 69
Outputs
Example
To generate an alarm when flow exceeds 300 l/min, and reset it when the flow drops below 280 l/min, set Direction to Rising,
Activation Level to 300 l/min and Deactivation Level to 280 l/min.
About Negative Flows
While operating on negatives flows is possible, it is not recommended because of the potential confusion it can cause. A larger
negative flow is actually smaller number. For example, a Falling value always refers to a number that is becoming smaller, hence
-280 falls to -300.
To generate an alarm when the flow exceeds 300 l/min in the reverse (negative) direction and have it reset only when the volume
48
1.
Select Output.. from the Options menu.
Use the UP/DOWN arrow keys to select Digital Device
2.
1/2/3 Setup. Press the ENTER key. The Output 1/2/3 menu
is displayed.
3.
Use the UP/DOWN arrow keys to select Function. Press the
ENTER key.
4.
Use the UP/DOWN arrow keys to scroll through the output
types. Select Alarm Output.
Use the UP/DOWN arrow keys to select Measurement
5.
Source.
6.
Choose from Volume, Flow, Energy, Power or Signal.
7.
Use the UP/DOWN arrow keys to select Continue..
8.
According to your choice in step 6, complete the alarm
configuration as described in the following sections.
Volume Alarm
9.
Use the UP/DOWN arrow keys to select Direction. You may
select a Rising or Falling value (as volumes generally only
rise until reset, Rising is the usual choice).
10.
Use the UP/DOWN arrow keys to select Activation Level.
Set the volume limit for the alarm on this output.
11.
If required, set a Deactivation Level although this has no
effect until the volume totals are reset.
12.
Use the UP/DOWN arrow keys to select Save Setup and
Exit..
Energy Alarm
9.
Use the UP/DOWN arrow keys to select Direction. Select
Rising. The device only supports positive energy (an energy
loss if operating as a heater, or an energy gain if operating
as a chiller).
10.
Use the UP/DOWN arrow keys to select Activation Level.
Set the energy limit for the alarm on this output.
11.
If required, set a Deactivation Level although this has no
effect until the energy total is reset.
12.
Use the UP/DOWN arrow keys to select Save Setup and
Exit..
Flow Alarm
9.
Use the UP/DOWN arrow keys to select Direction. Select
Rising to trigger an alarm when a certain flow is exceeded
or Falling to trigger an alarm when a certain flow is not
achieved.
10.
Use the UP/DOWN arrow keys to select Activation Level.
Set the flow limit for the alarm on this output.
11.
Set a Deactivation Level (the value at which an alarm is
canceled).
If the direction is set to Rising, the alarm is triggered when
the flow exceeds the Activation Level. The Deactivation
Level must be a value less than or equal to the Activation
Level.
If the direction is set to Falling, an alarm is triggered when
the flow drops below the
Activation Level. The Deactivation Level must be a value
greater than or equal to the Activation Level.
12.
Use the UP/DOWN arrow keys to select Save Setup and
Exit.
Operating Instructions

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Pf330 v2

Inhaltsverzeichnis