Herunterladen Inhalt Inhalt Diese Seite drucken

Position - Wilo EHV G2 Einbau- Und Betriebsanleitung

Dn250
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
English
Guide pipe sizes and material versions
Type
DN 50/2RK
DN 65/1RK
DN 65/2RK
DN 80/2RK
DN 100/2RK
DN 100S/2RK
DN 150L/2RK
DN 150S/2RK
DN 200/2R
DN 250/2R
DN 250S/2RK
Suspension units may not be used without guide pipes. Otherwise, the pump will slip
off the coupling base. This causes the connection between the coupling flange and
base to leak and the pump may be damaged. To prevent this, the use of guide pipes
is mandatory.
4.3.

Position

Together, the coupling base, guide pipe bracket and guide pipes form the suspension
unit. This is installed in the operating area and connected to the discharge-side pipe
system.
The connected pipe system must be self-supporting. This means it must not be
supported by the coupling base.
The coupling flange is mounted on the discharge flange of the pump. It has guide claws
to guide it along the guide pipe so that the pump can be connected to the coupling
base.
The coupling flange is automatically connected to the coupling base by the weight of
the pump.
A sealing ring is inserted in the coupling flange to ensure that there is no leakage be-
tween the coupling flange and the coupling base. The sealing ring is pushed against the
coupling base during operation, thus sealing the connection.
To ensure unimpaired operation, the suspension unit must be installed vertically
in the operating area.
32
Number
Material
2x
A2
1x
A2
2x
A2
2x
A2
2x
A2
2x
A2
2x
A2
2x
St 33
2x
A2
2x
A2
2x
St 33
PRODUCT DESCRIPTION
Size* in mm
(*Outer Ø x wall thickness)
26.9x2
26.9x2
26.9x2
42.4x2
42.4x2
42.4x2
42.4x2
60.3x3.65
42.4x2
42.4x2
60.3x3.65
WILO SE 11/2016 Ed.01 DIN A5

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis