Herunterladen Inhalt Inhalt Diese Seite drucken

Structure Components - IFM Electronic ecomot100 CR2511 Gerätehandbuch

Ausgangs-modul
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Data structure:
CR2511 ConfigStruct
Purpose:
Parameter and configuration data
can be written or read.
The data structure is assigned to the
function input "CFG_DATA" via the
ADR operator.

Structure components

Name
Data type
GUARDTIME
TIME
LIFETIME
BYTE
Ch1
BYTE
Ch2
BYTE
Ch3
BYTE
Ch4
BYTE
Ch5
BYTE
Ch6
BYTE
Ch7
BYTE
Ch8
BYTE
PwmFrq
BYTE
Note:
All manuals and user guides at all-guides.com
Description
Guarding time of the module [msec.]
Lifetime of the module
Config. channel 1
Config. channel 2
Config. channel 3
Config. channel 4
Config. channel 5
Config. channel 6
Config. channel 7
Config. channel 8
PWM frequency in Hz
Range = 20 to 250 Hz (100 Hz)*
Mode 5 is only available if connection is made via the outputs with
current monitoring (see also page 30, Wiring).
*) default
OUTPUT MODULE
TYPE CR2511 ConfigStruct
STRUCT
GUARDTIME: TIME;
LIFETIME: BYTE;
Ch1: BYTE;
(*2000/1*) (*0,2,4,5*)
Ch2: BYTE;
(*2000/2*) (*0,2,4,5*)
Ch3: BYTE;
(*2000/3*) (*0,2,4,5*)
Ch4: BYTE;
(*2000/4*) (*0,2,4,5*)
Ch5: BYTE;
(*2000/5*) (*0,2,4,5*)
Ch6: BYTE;
(*2000/6*) (*0,2,4,5*)
Ch7: BYTE;
(*2000/7*) (*0,2,4,5*)
Ch8: BYTE;
(*2000/8*) (*0,2,4,5*)
PwmFrq: BYTE; (*2001/0*)
END_STRUCT
END_TYPE
0 = disabled (OFF)
2 = binary output *
4 = analog output (PWM)
5 = analog output (PWM; current-controlled)
0, 2*, 4, 5 (see Ch1)
0, 2*, 4, 5 (see Ch1)
0, 2*, 4, 5 (see Ch1)
0, 2*, 4, 5 (see Ch1)
0, 2*, 4, 5 (see Ch1)
0, 2*, 4, 5 (see Ch1)
0, 2*, 4, 5 (see Ch1)
CR2511