M
ANUAL
O
PTIONS
F
. 52
UNCTION NO
NORMALLY
NORMALLY
OPEN
CLOSED
0
-
(default
value)
1
-
• Normally open: The signal comes in when the contact is closed.
• Normally closed: The signal comes in when the contact is broken.
O
PTIONS
F
. 60
UNCTION NO
NORMALLY
NORMALLY
OPEN
CLOSED
1
51
(default
value)
2
52
3
53
4
-
5
-
6
-
Version: 4.0 (10-11-2011)
3.5.3 Control panel input settings and options
W
ORKING OF THE INPUT
EFFECT ON
INCOMING SIGNAL
The air curtain is or continues to
be switched On. You can switch it
Off using the
key.
The air curtain is always switched
On.
The display reads
.
The
key does not work (even in pause mode).
3.5.4 Unit input settings and options
W
ORKING OF THE INPUT
EFFECT ON
INCOMING SIGNAL
The air curtain is or continues to
be switched Off.
This works only in units to which
the input signal is directly
connected (locally).
The air curtain operates 1 strength
up, if switched on.
The display reads
.
The air curtain operates 2
strengths up, if switched on.
The display reads
.
The discharge air temperature is
increased by.
The display reads
.
The heating is reduced to the half
temperature.
The display reads
.
The heating is switched off.
The display reads
.
EFFECT ON
RELEASED SIGNAL
The air curtain is or continues to
be switched Off. You can switch it
On using the
key.
The air curtain is always switched
Off.
EFFECT ON
RELEASED SIGNAL
The unit operates according to the
control panel settings.
The release delay (function no. 76)
does not work.
The unit operates according to the
control panel settings.
The unit operates according to the
control panel settings.
The unit operates according to the
control panel settings.
The unit operates according to the
control panel settings.
The unit operates according to the
control panel settings.
37