M
ANUAL
N
.
F
O
UNCTION
58
Installation level
This function has a fixed value for the
types CA S.
60
Working of the external-control input
in the unit
61
Working of the external-control out-
puts in the unit
62
No function
63
No function
64
No function
65
PID factors for temperature control in
the unit
66
67
69
Room temperature reading in the
display
See also section 3.4.
70
Version of the control panel software
71
Resetting the control panel
Use this function:
• to remedy fault E1 or E2 (see
section 5.4);
• after replacing a printed circuit
board (see section 6.8);
• after removing or replacing a
connected unit.
72
Show/do not show faults F1, F2 and F3
on the display. These faults can be
caused by external factors and do not
necessarily affect the operation of the
air curtain.
Version: 4.0 (10-11-2011)
O
PTIONS
0 = level A for favourable conditions
(lower discharge air velocity and sound
level, only CA)
1 = level B for normal conditions
(default value, only CA)
2 = Setting for use with CA
for units with unit code 3xxx)
See section 3.5.4.
See section 3.5.6.
Do not change these settings, unless on Biddle's
instructions.
0 = no reading
1 = reading (default value)
The version number is displayed.
(no options)
dF = all functions have default values
-- = there are functions with deviating values
To reset:
• press
and
simultaneously.
You return to the user's level immediately.
This will default all values at the installer's
level. Note down your settings before-
hand.
0 = do not report faults F1, F2 and F3
1 = report all faults (default setting)
2 = do not report fault F1
3 = do not report faults F2 and F3
Faults that are not reported cannot be read
out via function 10 of the controller's menu
either.
Y
OUR
SET
TING
. (default value
2
-
X
X
X
X
33