Herunterladen Inhalt Inhalt Diese Seite drucken

salmson Smart Control SC-L Einbau- Und Betriebsanleitung Seite 45

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

English
Menu 4: Display of current settings and basic switchgear data
No.
4.2.3.0 Unit switching cycles
4.2.4.x Switching cycles of the individual pumps
4.3.0.0 Details of switchgear
4.3.1.0 Switchgear type
4.3.2.0 Serial number (as ticker format)
4.3.3.0 Software version
4.3.4.0 Firmware version
Menu 5: Basic switchgear settings
No.
Description
5.0.0.0 Basic settings
5.1.0.0 Communication
5.1.1.0 Modbus
Baud rate
5.1.1.1
Values: 9.6, 19.2, 38.4, 76.8
Factory setting: 19.2
Slave address
5.1.1.2
Value range: 1 ... 247
Factory setting: 10
Parity
5.1.1.3
Values: even, non, odd
Factory setting: even
Stop bits
5.1.1.4
Values: 1, 2
Factory setting: 1
5.1.2.0 BACnet
Baud rate
5.1.2.1
Values: 9.6, 19.2, 38.4, 76.8
Factory setting: 19.2
Slave address
5.1.2.2
Value range: 1 ... 255
Factory setting: 128
Parity
5.1.2.3
Values: even, non, odd
Factory setting: even
Stop bits
5.1.2.4
Values: 1, 2
Factory setting: 1
Description
Display
Menu 5: Basic switchgear settings
No.
Description
BACnet Instance Device ID
5.1.2.5
Value range: 0 ... 9999
Factory setting: 128
5.1.3.0 GSM**
5.2.0.0 Sensor settings
Measurement range
5.2.1.0
Value range: 0 ... 12.50
Factory setting: 2.50
Sensor type
Values: 0-10V, 2-10V, 0-20mA,
5.2.2.0
4-20mA
Factory setting: 4-20mA
Priority when dry run and high water
signals are present simultaneously**
5.2.5.0
Values: Dry Run, High Water
Factory setting: Dry Run
Signal detection for level control**
5.2.6.0
Values: Floater, Sensor
Factory setting: Sensor
5.4.0.0 Limit values
Dry run level
5.4.1.0
Value range*: 0.01 ... 12.39
Factory setting: 0.12
High water alarm level
5.4.2.0
Value range*: 0.12 ... 12.50
Factory setting: 1.50
High water alarm delay
5.4.4.0
Value range: 0 ... 30
Factory setting: 0
Running time monitoring of individual
pumps
5.4.5.0
Values: ON, OFF
Factory setting: OFF
Max. running time of individual pumps
5.4.6.0
Value range: 0 ... 60
Factory setting: 10
Behaviour in case of mains connection
errors**
5.4.7.0
Values: OFF, Message, Stop Pumps
Factory setting: Stop Pumps
Behaviour on activation of thermal
motor winding monitoring**
5.4.8.0
Values: Auto Reset, Manu Reset
Factory setting: Auto Reset
45
Display

Werbung

Inhaltsverzeichnis
loading

Verwandte Produkte für salmson Smart Control SC-L

Inhaltsverzeichnis