Herunterladen Inhalt Inhalt Diese Seite drucken

salmson Smart Control SC-L Einbau- Und Betriebsanleitung Seite 44

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

English
Menu 1: Control parameters
No.
Description
Peak-load pump 1 off
1.2.2.4
Value range: 0.06 ... 12.42
Factory setting: 0.50
Peak-load pump 2 on
1.2.2.5
Value range: 0.09 ... 12.45
Factory setting: 1.00
Peak-load pump 2 off
1.2.2.6
Value range: 0.06 ... 12.42
Factory setting: 0.75
Peak-load pump 3 on
1.2.2.7
Value range: 0.09 ... 12.45
Factory setting: 1.25
Peak-load pump 3 off
1.2.2.8
Value range: 0.06 ... 12.42
Factory setting: 1.00
Delay times for activation and deacti-
1.2.5.0
vation of the pumps
Base-load pump stop delay
1.2.5.1
Value range: 0 ... 60
Factory setting: 5
Peak-load pump(s) activation delay
time
1.2.5.2
Value range: 1 ... 30
Factory setting: 3
Peak-load pump(s) stop delay
1.2.5.3
Value range: 0 ... 30
Factory setting: 1
Stop delay at dry-running level
1.2.5.4
Value range: 0 ... 10
Factory setting: 0
Activation delay time after dry run
1.2.5.5
Value range: 0 ... 10
Factory setting: 1
System activation delay time after
power interruption
1.2.5.6
Value range: 0 ... 180
Factory setting: 0
Menu 2: Communication parameters
No.
Description
2.0.0.0 Communication
Field bus
2.1.0.0
Values: None, Modbus, BACnet, GSM
Factory setting: None
Menu 3: Pump activation
No.
Display
3.0.0.0 Pump activation
Switching automatic mode on/off
3.1.0.0
Values: ON, OFF
Factory setting: OFF
3.2.0.0. Operating mode per pump
3.2.x.0 Selection of pump 1 ... 4
Operating mode, pump 1
3.2.1.1
Values: OFF, HAND, AUTO
Factory setting: AUTO
Operating mode, pump 2
3.2.2.1
Values: OFF, HAND, AUTO
Factory setting: AUTO
Operating mode, pump 3
3.2.3.1
Values: OFF, HAND, AUTO
Factory setting: AUTO
Operating mode, pump 4
3.2.4.1
Values: OFF, HAND, AUTO
Factory setting: AUTO
Menu 4: Display of current settings and basic switchgear data
No.
4.1.0.0 Current operating values
4.1.1.0 Current level
4.1.2.0 Current control values
4.1.2.1 Base-load pump on
4.1.2.2 Base-load pump off
4.1.2.3 Peak-load pump 1 on
4.1.2.4 Peak-load pump 1 off
4.1.2.5 Peak-load pump 2 on
4.1.2.6 Peak-load pump 2 off
4.1.2.7 Peak-load pump 3 on
4.1.2.8 Peak-load pump 3 off
Display
4.1.4.0 Limit values
4.1.4.1 Dry-running protection level
4.1.4.2 High water alarm level
4.2.0.0 Operating data
4.2.1.0 Total running time of the system
4.2.2.x Running time of the individual pumps
44
Description
Description
Display

Werbung

Inhaltsverzeichnis
loading

Verwandte Produkte für salmson Smart Control SC-L

Inhaltsverzeichnis