• 1 - 4 inputs for thermal winding monitoring (bimetal or
PTC temperature sensor)
• 2 inputs for electrodes for leakage detection or humidity
sensors for the connected pumps
• 1 digital input (External OFF) for remote activation and
deactivation of automatic mode
3.5.2. Outputs
• 1 potential-free contact for SSM and SBM
• 1 potential-free contact for the high water alarm
• 1 potential-free contact for starting an external consumer
(e.g. submersible mixer) depending on standstill times of
the connected pumps
• 1 analogue output 0 - 10 V, for display of the level actual
value
3.5.3. Switchgear
Mains connection:
Max. current consumption:
Max. switching capacity:
Max. fuse protection on mains
side:
Activation type:
Ambient/operating tempera-
ture:
Storage temperature:
Max. relative humidity:
Protection class:
Control voltage:
Alarm contact switching
capacity:
Housing material:
Electrical safety:
3.6.

Type key

Salmson-Smart Control
Example:
SC-L 2x12A-M-DOL-WM-Ex
Version:
SC
SC = Smart Control switchgear for fixed-speed
pumps
L
Level-dependent control of pumps
2x
Max. number of pumps that can be connected
12A
Max. rated current in ampere per pump
Mains connection:
M
M = alternating current (1~230 V)
T4 = three-phase current (3~ 400 V)
Pump activation type:
DOL
DOL = direct-on-line starting
SD = star-delta activation
See rating plate
See rating plate
See rating plate, AC3
See rating plate
See rating plate
0 to 40 °C
-10 to +50 °C
50 %
IP 54
24 VDC, 230 VAC
max. 250 V, 1 A
Steel sheeting, powder-coated
exterior
Dirt level II
Installation type:
WM = wall-mounted installation
WM
BM = floor model
OI = outdoor installation with pedestal
Version for pumps and signal transmitters used in
Ex
potentially explosive areas
3.7.

Options

• Connection for 3 or 4 pumps
• Customer-specific adjustments for special applications
3.8.

Scope of delivery

• Switchgear
• Wiring diagram
• Test protocol in accordance with EN 60204-1
• Installation and operating instructions
3.9.
Accessories
• Float switch for wastewater and sewage free of faeces
• Float switch for abrasive sewage containing faeces
• Level sensors
• Printed circuit board for ESM and EBM
• Horn 230 V, 50 Hz
• Flash light 230 V, 50 Hz
• Signal lamp 230 V, 50 Hz
Accessories have to be ordered separately.
4.

Transport and storage

4.1.

Delivery

On delivery, check immediately that the shipment is complete and
undamaged. If any parts are damaged or missing, the transport
company or the manufacturer must be notified on the day of de-
livery. Claims made after this date cannot be recognised. Damage
to parts must be noted on the delivery or freight documentation.
4.2.

Transport

Only the packaging used by the manufacturer or supplier may be
used for transport. This normally precludes the possibility of dam-
age occurring during transport and storage. The packaging should
be stored in a safe place for reuse if the product is frequently used
at different locations.
4.3.

Storage

On delivery, switchgears may be placed into temporary storage for
up to 1 year until use providing the details below are observed.
The following should be taken into consideration for storage:
• Place the packaged switchgear on a firm subsurface.
• Our switchgears may be stored from -10 °C to +50 °C at
a max. relative air humidity of 50 %. The store room must
be dry. We recommend a frost-protected room for storage
with a temperature between 10 °C and 25 °C and a relative
air humidity of 40 % to 50 %.
Avoid formation of condensate!
• Seal the threaded cable connections securely to prevent
ingress of moisture.
• Connected power supply cables should be protected
against kinking, damage, and moisture.
37