8. Startup

Start up Conlift in accordance with local
Note
regulations and accepted codes of good
practice.
1. Check that all hoses and connections are tight.
2. Connect the power supply.

8.1 Checking the function

Pump operation
Press the manual test button.
Alarm
1. To ensure that the alarm level is reached,
squeeze the discharge hose (or close the
isolating valve, if fitted), and fill water into the
tank. The pump will be started via the float
switch.
2. Continue filling water into the tank until the safety
overflow switch is activated. If no external alarm
is connected to Conlift, this function can be
checked by means of a multimeter.
The safety overflow switch must be
Note
activated before the water starts running
out of Conlift.
3. Stop filling water into the tank and stop
squeezing the discharge hose. The alarm stops
(the switch opens). The pump continues
operating. When the stop level is reached, the
pump will stop.
After checking the function, push the inlet hose back
into the lifting station and let the condensate from the
boiler or air-conditioning system run into the tank
again.

9. Maintenance and service

Warning
Conlift must only be serviced by trained
service personnel.
Always use original accessories from
Grundfos to ensure safe and reliable
operation.
Warning
If the power supply cable is damaged, it
must be replaced by the manufacturer, the
manufacturer's service partner or similarly
qualified person.

9.1 Maintenance

Conlift does not require any special maintenance,
but we recommend to check operation and pipe
connections at least once a year and to check and
clean the collecting tank, if necessary.
Conlift2 pH+
Check the state of the granulate regularly.
Check the level of acid in the condensate with the
supplied pH indicator twice a year.
See section
9.2

Service.

9.2 Service
Thanks to the Conlift design, service can easily be
performed in case of malfunction or blocked pump.
Warning
Conlift must only be serviced by trained
service personnel.
Warning
Before starting any service work, remove
the fuse, pull out the plug, or switch off the
power supply. Make sure that the power
supply cannot be accidentally switched on.
All rotating parts must have stopped
moving.