Commissioning
5
Commissioning
5.1
General information
General information
•
When using meter with fluids carefully remove the air to prevent gas bubbles.
•
When using meter with gases increase the flow pressure slowly.
•
Vary the flow with help of adjustable valves (control valves) to protect the float from pressure
shock waves. Otherwise, the flowmeter may be damaged.
•
The optional use of gas damping may not be used to compensate for shock waves.
Inspection prior to switching on auxiliary power
Prior to commissioning the unit, check the following:
•
The wiring is correctly implemented according to the connection diagram, see chapter
"Electrical connection",
•
The flowmeter is grounded properly,
•
The ambient conditions meet specifications,
•
The auxiliary power must match information on the model plate.
Inspection after switching on auxiliary power
After commissioning perform the following step:
•
Check and configure the measurement parameters according to operating conditions.