Micropulse Transducer in a Flat Profile Housing
4
Installation and connection (continued)
4.4

Electrical connection

Pin
Color
1
Brown
2
-
3
Blue
4
Black
Unassigned leads can be connected to the GND on the controller side but not to the shield.
1)
Tab. 4-2:
Pin assignment of S4 connector
4.5

Cable routing

Defined ground!
The transducer and the control cabinet must be
at the same ground potential.
Magnetic fields
The position measuring system is a magnetostrictive
system. It is important to maintain adequate distance
between the transducer and strong, external magnetic
fields.
Cable routing
Do not route the cable between the transducer, controller,
and power supply near high voltage cables (inductive stray
noise is possible).
Inductive stray noise from AC harmonics (e.g. from phase
angle controls) are especially critical and the cable shield
offers very little protection against this.
Cable length
Max. cable length 20 m. Longer cables may be used if
their construction, shielding and routing prevent noise
interference.
10
english
BTL6-U110-...S4
L+ (18
30 V)
...
Not used
1)
L- (GND)
C/Q (communication line)
3
2
4
1
Fig. 4-8:
Pin assignment of S4 connector (view from
above on transducer)