Parameter Data - Balluff BTL6-U110-M0500-PF-S4 Betriebsanleitung

Micropulse wegaufnehmer im profilgehäuse flach btl6-u110-m_ _ _ _-pf-s4 serie
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
BTL6-U110-M _ _ _ _ -PF-S4
Micropulse Transducer in a Flat Profile Housing
6
IO-Link interface (continued)
6.4

Parameter data

Index
Subindex Parameter
0x0010
0
0x0011
0
0x0012
0
0x0013
0
0x0014
0
0x0015
0
0x0016
0
0x0017
0
0x000C 0
0x000D 0, 1, 2
0x000E
0
0x0018
0
0x0040
0
0x0041
0
Tab. 6-3:
Parameter data of IO-Link interface
Access to subindex 0 address the entire object
of an index. Access of subindices >0 addresses
the individual elements of an index.
Device Access Locks
With this standard parameter, it is possible to active or
deactivate certain functions of the IO-Link device. With
BTL6-U110-..., there is the option to lock the function of
the parameter manager. To do so, bit 1 of the 2 byte value
must be set to "1" (locked). In order to unlock the
parameter manager, bit 1 is set to "0".
Bit 0
"Lock parameter access" –
not supported
Bit 1
"Lock Parameter Management" –
supported
Bit 2
"Lock local parameterization" –
not supported
Bit 3
"Lock local user interface" –
not supported
Bit 4 to 15
Reserved
Tab. 6-4:
Lock parameter data
14
english
Size
Vendor name
7 bytes
Vendor Text
15 bytes
Product Name
Max.
40 bytes
Product ID
12 bytes
Product Text
27 bytes
Serial number
Max.
18 bytes
Hardware Revision
2 bytes
Firmware Revision
9 bytes
Device Access Locks
2 bytes
Profile Characteristic
4 bytes
PD Input Descriptor
3 bytes
Application Specific Tag
32 bytes
Null point offset
4 bytes
Takeover of null point
Boolean
offset
(1 byte)
Access
Parameter
management
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read/Write
Yes
Read Only
No
Read Only
No
Read/Write
Yes
Read/Write
No
Write Only
No
Profile Characteristic
This parameter indicates which profile is supported by the
IO-Link device.
The BTL6-U110-... transducer supports the Smart Sensor
Profile with a process data variable:
Subindex 1 ("Profile Identifier -> DeviceProfileID"):
0x0001 ("Smart Sensor Profile")
Subindex 2 ("Profile Identifier -> FunctionClassID"):
0x8000 ("Device Identification Objects")
Subindex 3 ("Profile Identifier -> FunctionClassID"):
0x8002 ("ProcessDataVariable")
PD Input Descriptor
This parameter describes the composition of the process
data variables used.
The BTL6-U110-... transducer processes the process
data variable as follows:
Subindex 1: 0x032000
0x03 -> Data type = IntegerT
0x20 -> Data size = 32 bits
0x00 -> Offset = 0 bits
Application Specific Tag
The "Application Specific Tag" makes it possible to assign
the IO-Link device an arbitrary, 32-byte string. This can
only be used for application-specific identification and
applied in the parameter manager. The entire object is
accessed via subindex 0.
Default value
"BALLUFF"
"www.balluff.com"
"BTL6-U110-Mxxxx-
PF-S4"
"BTL6PFIOLxxx"
"Balluff Position
Transducer"
"YYMMDDXXXXXXXX"
"XX"
"vX.XX.XXX"
0x00 0x01 0x80 0x02
0x03 0x20 0x00
0