2. Transport/Storage

The pumps are supplied from the factory
in appropriate packing.
Warning
Pumps with electronic components should
be protected from moisture.

3. Intended application

Circulation pumps with integrated frequency converter
HXC 501, LXC 655 (single pumps)
HXCD 501, LXCD 655 (twin pumps)
are used to circulate liquids in
– hot-water heating systems
– closed industrial circulation systems
They are glandless and not suitable for secondary
hot water services.
Heating water in accordance with VDI 2035, water/glycol mixture
with up to 50% glycol ratio. The pumps must not be used
in the food sector nor for drinking water.

3.1 Operating temperature/Operating pressure

Permissible water temperature: +15 °C to +95 °C
Permissible operating pressure: max. 16 bar
Ambient temperature:
Noise level:
Protection:

4. Assembly

4.1 Flushing out the heating system (with pump removed)
In order to avoid undesirable interruptions in operation
and non-starting of the pump after long periods of standstill,
it is recommended for a newly-installed or converted heating
system that the system be drained, flushed through well
and then refilled again after heating up for the first time.
The system must comply with the latest state of technology.
(Positioning of expansion vessel or initial safety feed.)
4.2 Antifreezers (as far as necessary)
Important: Flush the piping network through particularly well
before the antifreeze mixture is filled.
Follow the antifreeze supplier's instructions with respect to mixing
and filling, as well as the choice of material in the piping and
apparatus network (pay particular attention to protection against
corrosion!). Water/glycol mixture up to 50% glycol ratio permissible.
Over 10% glycol ratio, correct the pumping data of the pumps
accordingly.
max. 40 °C
< 70 dB (A)
IP 42