Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens SIMOVERT MASTERDRIVES Betriebsanleitung Seite 270

Vorschau ausblenden Andere Handbücher für SIMOVERT MASTERDRIVES:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

08.2009
Water-cooled
inverter
Order No.
Rated input voltage DC 510 to 620 V
6SE7021-3TB 1-1AA1
6SE7021-8TB 1-1AA1
6SE7022-6TC 1-1AA1
6SE7023-4TC 1-1AA1
6SE7023-8TD 1-1AA1
6SE7024-7TD 1-1AA1
6SE7026-0TD 1-1AA1
6SE7027-2TD 1-1AA1
NOTE
Siemens AG
6SE7087-6KD50
SIMOVERT MASTERDRIVES
Power loss
Cooling-
(at 2.5 kHz)
water
require-
ment
[kW]
[l/min]
0.21
1.00
0.16
1.20
0.33
2.10
0.47
2.60
0.58
4.25
0.71
4.80
0.86
5.25
1.07
6.00
= 5 corresponds to MASTERDRIVES Motion Control
= 7 corresponds to MASTERDRIVES Motion Control Performance 2
Table 11-5
Water-cooled inverter
These units and the air-cooled inverters are identically constructed.
Instead of the heat sink for air, an air/water cooler has been installed.
All the technical data not listed in Table 11-5 for a particular unit are the
same as those of the air-cooled inverter. The first 12 positions of the
Order No. are identical. The supplement "-1AA1" indicates water
cooling.
*)
The cooling water requirement applies for the unit rating of the inverter and 100%
utilization of the additional heat dissipation obtained from a water temperature rise
intake/return of ∆T = 5 K.
Operating Instructions
Maximum
additional heat-
dissipation power
*)
at Tair ≤ 30 °C
[kW]
0.1
0.1
0.2
0.2
0.5
0.5
0.5
0.5
Technical Data
Typical pressure drop
according to volumetric flow
0.15 to 0.2 bar at 1.2 l/min
0.15 to 0.2 bar at 1.2 l/min
0.15 to 0.2 bar at 2.6 l/min
0.15 to 0.2 bar at 2.6 l/min
0.15 to 0.2 bar at 6.0 l/min
0.15 to 0.2 bar at 6.0 l/min
0.15 to 0.2 bar at 6.0 l/min
0.15 to 0.2 bar at 6.0 l/min
11-7

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Simovert masterdrives

Inhaltsverzeichnis