Connecting-up
DC link connection
U1 V1 W1 PE1 C
D
L1 L2 L3
L+
L-
X2 - Motor
connection
T1 T2 T3
U2 V2 W2 PE2
NOTE
7-6
The connection for the DC link is provided on the top of the unit on a
terminal block.
Terminal
Designation
1
U1 / L1
2
V1 / L2
3
W1 / L3
4
PE1
5
C / L+
6
D / L-
Terminal 1 is at the left when installed.
Table 7-3
DC link connection
The motor connection is located at the lower section of the unit.
Terminal
Designation
1
U2 / T1
2
V2 / T2
3
W2 / T3
4
PE2
Terminal 1 is at the left when installed.
Table 7-4
Motor connection
For inverters of type D, a fan is installed with a voltage of 230 V for
which an external auxiliary voltage has to be connected up at fuses
F101 and F102.
Meaning
These terminals
are not
internally connected
Protective conductor
connection
DC link voltage +
DC link voltage -
Meaning
Phase U2 / T1
Phase V2 / T2
Phase W2 / T3
Protective conductor
connection
6SE7087-6KD50
Operating Instructions
SIMOVERT MASTERDRIVES
08.2009
Range
DC 510 - 650 V
DC 510 - 650 V
Range
3AC 0 - 480 V
3AC 0 - 480 V
3AC 0 - 480 V