Technical Data
Designation
Order number 6SE70...
Rated voltage
Input
Output
Rated frequency
Input
Output
Rated current
Input
Output
DC link voltage
Rated output
[kVA] 22.4...27.1 24.7...29.9 30.9...37.4 38.8...47.0 47.4...57.4
Auxiliary current supply
Pulse frequency
[kHz]
Load class II to EN 60 146-1-1
Base load current
Overload current
Cycle time
Overload duration
Losses, cooling, power factor
Power factor
Converter cosϕU
Efficiency η
Pulse frequency 5 kHz
Dissipated losses
[kW]
Pulse frequency 5 kHz
Cooling air required
[m³/s]
Sound pressure level, dimensions, weights
Sound pressure level [dB(A)]
Type of construction
Width
Height
[mm]
Depth
Weight approx.
11-6
23-4TC 1
23-8TD 1
[V]
[Hz]
[A]
40.5
44.6
34.0
37.5
[V]
[V]
DC 24 (20 -30) (2.0 A without options; more with options)
< 0.92 ind. < 0.92 ind. < 0.92 ind. < 0.92 ind. < 0.92 ind.
0.98
0.98
0.59
0.70
0.028
0.054
60
65
C
D
180
270
600
600
350
350
[kg]
21
32
= 5 corresponds to MASTERDRIVES Motion Control
= 7 corresponds to MASTERDRIVES Motion Control Performance 2
Table 11-4
Technical data
Value
24-7TD 1
26-0TD 1
DC 510 to 650 (-15 % / +10 %)
3 AC 0 up to rated input voltage x 0.64
---
0 ... 400
55.9
70.2
47.0
59.0
= rated DC voltage
5.0
0.91 x rated output current
1.6 x rated output current
300 s
30 s
0.98
0.98
0.87
1.02
0.054
0.054
65
D
270
270
600
600
350
350
32
Operating Instructions
27-2TD 1
85.7
72.0
0.98
1.27
0.054
65
65
D
D
270
600
350
32
32
6SE7087-6KD50
Siemens AG
SIMOVERT MASTERDRIVES
08.2009