WARNING
Siemens AG
6SE7087-6KD50
SIMOVERT MASTERDRIVES
The 9-pole terminal strip is used for connecting up a 24 V voltage
supply and for connecting up a main or bypass contactor and for the
"Safe STOP" function.
The voltage supply is required if the inverter is connected up via a main
or bypass contactor.
The connections for the contactor control are floating.
The "Safe STOP" function ensures that no rotating field can occurr at
the motor terminals, i.e. the motor cannot rotate. By opening the jumper
between terminals X9.5 and X9.6 (through an external contact), the
"Safe STOP" function is activated. The inverter is delivered with
jumpered terminals X9.5 and X9.6.
Terminal
Designation
1
+24 V (in)
2
0 V
3
n.c.
4
n.c.
5
n.c.
6
n.c.
7
Main contactor
control
8
n.c.
9
Main contactor
control
Connectable cross-section: 1.5 mm² (AWG 16)
Terminal 1 is at the front when installed.
Table 7-5
Connection of external aux. voltage supply DC 24 V, safe STOP, main
contactor control
The power terminals may still be live even if the "Safe STOP" function
is activated!
The relay on PEU -X9:7.9 is only suitable for switching voltages up to
30 V with a 9-pole terminal strip!
Operating Instructions
Description
24 V voltage supply
Reference potential
Not connected
Not connected
Not connected
Not connected
Main contactor control
Not connected
Main contactor control
Connecting-up
Range
DC24 V ≤ 2.5 A
DC 30 V
0.5 A
7-7