Herunterladen Inhalt Inhalt Diese Seite drucken

IFM Electronic CR2016 Gerätehandbuch Seite 22

Inhaltsverzeichnis

Werbung

CabinetModul CR2016
Index
S-Idx
Name
1008
0
device name
1009
0
HW Version
100A
0
SW Version
100C
0
guard time
100D
0
life time factor
1010
0
number of save
options
1
save parameter
1011
0
number of restore
options
1
restore default
parameter
1014
0
COB ID EMCY
1016
0
number of monitored
devices
1
consumer heartbeat
time
1017
0
producer heartbeat
time
1018
0
number of identity
objects
1
vendor ID
1400
0
highest numbered
subindex Receive
PDO 1
1
COB ID Receive
PDO 1
2
transmission type Rec
PDO 1
1401
0
highest numbered
subindex Receive
PDO 2
22
Typ
Default
ro
str
CR2016
ro
str
HW Vx�x
ro
str
SW Vx�x
rw
u16
0x0000
rw
u8
0x00
ro
u8
0x01
rw
u32
0x00000002
ro
u8
0x01
rw
u32
0x00000001
rw
u32
0x00000080 +
NodeID
ro
u8
0x01
rw
u32
0x00000000
rw
u16
0x0000
ro
u8
0x04
ro
u32
0x0069666D
ro
u8
0x02
rw
u32
0x00000200 +
NodeID
rw
u8
0x01
ro
u8
0x02
Beschreibung
time in ms
within this time the module expects a "node
guarding" of the network master
0 = node guarding deactivated
if no "node guarding" is received for "guard
time" x "life time", the module generates an
EMCY the result form "guard time" x "life
time" must be between 0 and 65535
0x00000000 = no save
0x00000001 = saving all parameters
after the string 'save' is written to this entry
0x00000002 = auto save
restore all parameters to default value after
next reset if the string 'load' is written to this
entry
module generates EMCY messages (bit 31
= 0)
heartbeat monitoring time for node n monito-
ring of only one node is supported
0x0nntttt = monitoring time [ms]
0x0nntttt = node number
(if nn or tttt = 0, no monitoring is carried out)
time interval [ms] where the module gene-
rates a producer heartbeat
PDO is valid (bit 31 = 0)
0x01���0xF0 = synch cyclic
0xFE���0xFF = asynch (immediately)

Werbung