Mounting the
condensation drain
hose
42
3.
Set up the unit and ensure that it is aligned horizontally. Note: The top edge must not be
inclined backwards as this may cause moisture damages.
Fig. 44: Setting up the unit horizontally
When the unit is delivered, the condensate drains are closed. When installing the unit, the
correct drain must be opened and a condensation drain hose must be fitted:
1.
Open the unit and check which operating mode (A/B) is set on the switch of the main
PCB. If necessary, adjust the switch position to your preferred operating mode.
Fig. 45: Checking the operating mode
INSTALLATION AND SERVICE MANUAL FOR PROFESSIONALS
B
A
Installation: Assembly