Operation: Temporary operating modes (override)

Temporary operating modes (override)

With the exception of the automatic bypass function, the temporary operating modes are
activated manually and temporarily override the settings of the selected main mode. The
temporary operating modes are stopped automatically by a timer or if certain conditions are
not met, but can also be deactivated manually (with the exception of the automatic bypass
function).
Bypass mode
In bypass mode, the bypass damper is opened, which will guide the airflow around the heat
exchanger. The outside air is thus guided into the dwelling without heat recovery. The bypass
(cooling)
mode can be activated in two ways:
Automatic bypass
When using the automatic bypass function, the bypass damper is automatically opened/
function
closed when the conditions for automatic bypass are met.
You can change the setpoints for the minimum outdoor temperature (Tmin, default setting:
15 °C) and max. indoor temperature (Tmax, default setting: 24 °C) via PC Tool or the Dantherm
HRC 4 remote control.
If the conditions for automatic bypass are met, the open status of the damper is indicated by
the continuous illumination of the corresponding LED.
Conditions for activating the automatic bypass function:
If one of the following conditions is met, the bypass is deactivated:
Waste of energy!
If the settings for the bypass temperature are too low, there is a risk that the unit will open the
bypass while the central heating inside the dwelling is active.
Manual bypass
If bypass/cooling is desired and the automatic bypass function is not activated, the bypass
function
can be activated manually.
The bypass is opened once the conditions for manual bypass are met within the set time peri-
od (default setting: six hours). The time period can be changed by means of the PC Tool.
Briefly pressing the bypass button activates/deactivates the manual bypass mode.
An active bypass mode (open damper) is indicated by the continuous illumination of the
corresponding LED.
Note: If the bypass mode is activated but the conditions for the open bypass damper are not
met, the activated bypass mode is not indicated by the LED.
Conditions that must be met to activate the automatic bypass function:
Automatic bypass function
Manual bypass function
The outdoor temperature is at least 2 °C below the extract air temperature
AND the outdoor temperature is above the setpoint (Tmin)
AND the extract air temperature is above the setpoint (Tmax).
The outdoor temperature is above the extract air temperature.
The outdoor temperature is at least 2 °C below the setpoint (Tmin).
The extract air temperature is at least 1 °C below the setpoint (Tmax).
NOTICE
The outdoor temperature is at least 2 °C below the extract air temperature
AND the outdoor temperature is above 9 °C
11