WI 65TU - WI 95TU
3)
The utility company blocking contactor (K22) with main
contacts and an auxiliary contact must be designed and
provided by the customer in accordance with the heat
pump output.
The NO contact of the utility company blocking contactor
is looped from the terminal strip X3/G to the plug-in termi-
nal X3/A1. CAUTION! Extra-low voltage!
4)
The contactor (K20) for the immersion heater (E10) of
mono energy systems (HG2) should be dimensioned ac-
cording to the radiator output and must be supplied by the
customer. It is controlled (230 V AC) by the heat pump
manager via terminals X2/N and X2/K20.
5)
The contactor (K21) for the flange heater (E9) in the do-
mestic hot water cylinder should be dimensioned accord-
ing to the radiator output and must be supplied by the cus-
tomer. It is controlled (230 V AC) by the heat pump
manager via terminals X2/N and X2/K21.
6)
The contactors mentioned above in points 3, 4 and 5 are
installed in the electrical distribution system.
7)
All installed electric cables must have permanent wiring.
8)
The heat circulating pump (M13) is activated via the con-
tact N1-J13/NO5. The connection points for the pump are
X2/M13 and X2/N. When using pumps where the switch-
ing capacity exceeds the output, a coupling relay must be
interposed.
9)
The auxiliary circulating pump (M16) is activated via the
contact N1-J16/NO9. The connection points for the pump
are X2/M16 and X2/N. A coupling relay is already inte-
grated in this output.
10) The domestic hot water circulating pump (M18) is acti-
vated via the contact N1-J13/NO6. The connection points
for the pump are X2/M18 and X2/N. When using pumps
where the switching capacity exceeds the output, a cou-
pling relay must be interposed.
11) The brine or well pump (M11) is activated via the contact
N1-J12/NO3. The connection points for the pump are X2/
M11 and X2/N. A coupling relay is already integrated in this
output.
12) The return sensor (R2) is integrated in the heat pumps for
indoor installation.
The heat pump manager is connected via the following ter-
minals: X3/GND and X3/R2.
13) The external sensor (R1) is connected to terminals X3/GND
and X3/R1.
14) The domestic hot water sensor (R3) is included with the
domestic hot water cylinder and is connected to terminals
X3/GND and X3/R3.
www.dimplex.eu
7.6.3 Connection of electronically
regulated circulating pumps
Electronically regulated circulating pumps have high starting
currents, which may shorten the service life of the heat pump
manager. For this reason, a coupling relay is installed or must be
installed between the output of the heat pump manager and
the electronically regulated circulating pump. This is not neces-
sary if the permissible operating current of 2 A and a maximum
starting current of 12 A are not exceeded in the electronically
regulated circulating pump or if express approval has been is-
sued by the pump manufacturer.
CAUTION!
It is not permitted to connect more than one electronically
regulated circulating pump via a relay output.
7.6.4 Circulating pump connection with
high performance
In many cases, the supply voltage of the pump is stuck on con-
tinuous current when using larger electronically controlled cir-
culating pumps (the manufacturer's information on the pump
being used should be taken into consideration). The pump is
then generally actuated using the Start/Stop input. This input is
operated with extra low voltage from the pump (a link cable is
usually inserted in the factory default of the pump). In order to
be able to actuate the input, a coupling relay with a floating
contact is required. This must be controlled with the pump
function of a 230 V relay output of the controller. Due to the
extra low voltage to be switched, a suitable relay with the ap-
propriate contact material (gilded) must be selected and inte-
grated on-site.
7.6.5 Frost protection
Regardless of the settings for the heat circulating pumps, they
always run in heating and frost protection mode. In systems
with multiple heating circuits, the 2nd and 3rd heat circulating
pump has the same function.
CAUTION!
To ensure that the frost protection function on the heat pump
works properly, the heat pump manager must remain
connected to the power supply and flow must be maintained
through the heat pump at all times.
CAUTION!
The primary pump (M11 – responsible for the heat source flow
rate) and the secondary pump (M16 – responsible for the
warm/cold water flow rate) must always be clamped to the
heat pump manager in all cases. This is the only way to ensure
the pump flows and returns necessary for operation and to
ensure that the necessary safety measures are in place.
452237.66.80 · FD 0509
English
EN-9