Herunterladen Diese Seite drucken

Waeco AirCon Service ASC 6300 G LE Bedienungsanleitung Seite 37

Vorschau ausblenden Andere Handbücher für AirCon Service ASC 6300 G LE:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 102
Wait...
Erase flash... Erased!
Writing
After the update, the A/C service unit sets the default settings:
Wait!
loading default
parameters
The A/C service unit then restarts and the standby menu appears.
5. Remove the USB flash drive.
The A/C service unit is ready for operation.
14.12 Cleaning and inspection
Clean the exterior of the A/C service unit with a damp cloth as required. If necessary, use a small amount of
dishwashing detergent. Do not use solvents or scouring agents.
Check the service hoses and the service couplings for damage regularly. Do not start up the A/C service unit
if it is damaged.
15 Troubleshooting
Problem
The display shows Warning! Inter‐
nal vessel overpressure!.
The display shows Warning! Inter‐
nal vessel filled.
The display shows Warning! Pres‐
sure inside the A/C system. Re‐
covery start!
The display shows Warning! Pres‐
sure inside the A/C system!
The display shows Not enough vac‐
uum! Carry on?
The display shows A/C system
leakage! Carry on?
The display shows Drained oil
glas emptying!
The display shows Warning! Not
enough vacuum for injection!
The display shows Quantity too
large. Fill internal vessel!
1
63488
7%
762751
Possible cause
Normal message that appears during
the recycling process.
The internal refrigerant container is too
full to hold the quantity to be extracted.
Normal message that appears at the
start of the vacuum process. There is
still pressure present in the air condi­
tioning system.
Message during the vacuum process.
There is pressure in the air condition­
ing system.
Message that appears during the vac­
uum process if the pressure in the air
conditioning system after 8 min is still
more than 50 mbar.
Message at the end of the vacuum
process. The air conditioning system
shows a vacuum loss of more than
120 mbar during the checking time.
This message appears during the ex­
traction or recycling process if there
is more than 150 mL of used oil in the
container.
Message that appears during the fill­
ing phase if the vacuum in the air con­
ditioning system is insufficient to end
the process.
Message that appears during the
process input if there is not enough
refrigerant in the internal container to
complete the process.
Suggested remedy
To continue, press ENTER for three
seconds. If this message appears re­
peatedly, notify customer services.
Drain the internal refrigerant container
in the proper manner.
No action is required. The process
continues automatically.
No action is required. The process
continues automatically.
Check the air conditioning system or
the connections between it and the A/
C service unit for leaks.
Check the air conditioning system or
the connections between it and the A/
C service unit for leaks.
Dispose of the content of the used oil
container in an environmentally re­
sponsible manner.
Check the air conditioning system or
the connections between it and the A/
C service unit for leaks.
Fill the refrigerant container.
    EN
37

Werbung

loading

Diese Anleitung auch für:

Aircon service asc 6400 g le