Device configuration, application setup
"Application -
Batch mode"
menu items
"Batch 1-4" submenu
Batch-specific settings.
Fig. 4:
Description
Start/stop
Control input
only if "Start/stop" - "Preset
counter"
Control input
only if "Start/stop" - "Per
control input"
Preset counter
only if "Start/stop" - "Preset
counter"
Switches relay
Default batch number
only if "Batch number" -
"Automatic"
24
Configurable parameters
(factory settings are highlighted in bold)
Setup - Application - Batch mode, "Batch x" submenu
Enter a unique description for the batch here (recommended when
several batches are running in parallel on the device.) If no data are
entered, the device generates a description automatically.
Text entry: max. 16-digit.
Specify how batches are started/ended.
"Per control input": the batch is started/ended externally via a
digital control input (effect: start/stop batch x).
"At device/barcode/fieldbus": the batch can be started/ended by
operating the device, using a barcode or remotely (PC software,
fieldbus).
"Preset counter": the batch can be started by operating the device,
using a barcode reader or control input. The batch is ended when
the counter value >= the default value.
Select the control input that starts the batch. Alternatively, the
batch can be started via on-site operation.
Note: The batch cannot be ended using this input. The assigned
input is automatically pre-configured!
Picklist: Switched off, Digital input x
Select the control input that starts/ends the batch.
Note: The assigned input is automatically pre-configured!
The input must be active during the batch. The minimum duration
of the batch is one second.
Picklist: Switched off, Digital input x
Select the counter that ends the batch.
Note: The assigned input is automatically pre-configured!
Picklist: Switched off, Analog input x, Digital input x, Maths x
The assigned relay is switched as long as the batch is running.
Picklist: Not used, Relay x (xx-xx)
Configure the default value of the batch number, to which the batch
number is set if it is reset via control input.
User input: max. 9-digit.
Graphic Data Manager
Direct
access
code
16060/000 to
16060/003
16061/000 to
16061/003
16069/000 to
16069/003
16062/000 to
16062/003
16062/000 to
16062/003
16065/000 to
16065/003
16066/000 to
16066/003