Device configuration, application setup
"System - Signal
analysis" menu
items
Alarm statistics
The following data can be determined by means of the signal analysis cycles (e.g. daily analysis):
• How often was the set point violated (frequency)
• How long was the set point violated (duration in operating hours format 0000h00:00)
Picklist: no, yes
Note:
• The alarm statistics are generated for every active signal analysis (same run time). Alarm statistics
• The alarm statistics are only generated for "analog" set points (upper, lower and gradient). No
• Set points can be set for the data of the alarm statistics. These set points can monitor the frequency
Group days
Set up how often the weekly, monthly or yearly analysis is to be calculated.
(only if "Alarm
"No": each individual alarm is counted.
statistics" - "Yes")
"Yes": the number of days within the analysis cycle in which at least one alarm took place.
Picklist: no, yes
26
2.4
Setup - System - Signal analysis (alarm statistics)
Setup in order to get signal analysis for a preset time range/cycle as well as the function to
manually reset the signal analysis.
NOTICE
Only settings relevant for batch mode are described here. For all the other signal analysis
functions, see the Operating Instructions.
Depending on the selected function, the device' s user interface adapts itself, so that each
time only parameters that are required for safe unit functioning have to be checked/set.
Fig. 6:
Setup - System - Signal analysis - Alarm statistics
(factory settings are highlighted in bold)
are not generated for externally controlled signal analysis for the time the analysis is not active.
statistics are generated for "set points at counter".
or duration of set point violation for the analysis duration. Configuration under "Setup ->
Application -> Set points -> Set point x -> Channel or type" (see Operating Instructions).
Configurable parameters
Graphic Data Manager
Direct
access
code
17030/000
17040/000