TeCHniCaL fUnCTiOnaL CHaraCTerisTiCs
Dual burner, able to operate alternately with natural gas or with
diesel (max viscosity 1.5°E at 20°C).
EC approval according to European Standard EN 676 for natural
gas and Standard EN 267 for diesel.
progressive/modulating two-stage operation with gas fuel, and
two-stage with diesel fuel.
Electronic command and control equipment Lamtec, equipped
with microprocessor.
Fuel flow rate / comburent air regulation by means of two
servomotors controlled by the electronic equipment
Combustion head with partial recirculation of combusted gases
with reduced emissions (class III according to EN 676 for natural
gas, class II according to EN 267 for diesel).
Air minimum and maximum flow rate regulation by means of
electric stepper servomotor with pause closure of shutter to
prevent any heat dispersion to flue.
Valve seal control functions according to European Standard
EN676 and power regulation functions (read carefully the
operating instructions given in the GUIDE supplied along with
the burner for further details about the equipment operations).
OPeraTing range
The operating ranges are obtained from test boilers corresponding
to Standard EN 267 and are indicative of the combination
burner-boiler. For correct working of the burner the size of the
combustion chamber must correspond to current regulations; if
not the manufacturers must be consulted.
TBmL 50 me
*
LpG minimum thermal power = 120 kW.
7 / 30
0006160034_201307
Thermal power of methane gas
Thermal power of diesel fuel