GAS SUPPLY LINE
The basic diagram of the gas supply line is shown in the figure below.
The gas train is certified in accordance with EN 676 Standard and
is supplied separately from the burner.
a manual shut-off valve and an anti-vibration joint must be
installed upstream of the gas valve, as shown in the diagram.
BasiC Diagram Of THe gas BUrner
1)
Manual shut-off valve
2)
Anti-vibration joint
3)
Gas filter
4)
Gas minimum pressure switch
5)
Safety valve
6)
pressure regulator
7)
Valves seal control device
8)
Operating valve
GAS TRAIN SUppLIED BY ThE MANUFACTURER
9)
Air adjustment servomotor
10) Air adjustment gate valve
11) Air pressure switch
12) Combustion head
13) Gas regulation butterfly valve
14) Gas regulation servo motor