Herunterladen Diese Seite drucken

baltur TBML 50 ME Bedienungsanleitung Seite 13

Zweistoffbrenner gas / gasöl mit elektronischer modulation mit steuergerät bt 340

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 123
PiPe siZing Diagrams TBmL 50 me
pUMp AXIS
pUMp AXIS
graViTY sUPPLY sYsTem
1
Tank
2
Feeding pipe
3
Wire-net filter
4
pump
5
Degassifier
DrOP-TYPe sYsTem WiTH sUPPLY frOm THe TanK TOP
1
Tank
3
Wire-net filter
4
pump
6
Suction pipe
7
Return pipe
pUMp AXIS
inTaKe sUPPLY sYsTem
nOTe. For any components missing in the pipes, comply with current regulations.
h = Difference in level between level in the tank and the pump axis.
L = Maximum length of suction pipe including the vertical lift.
Deduct 0.25 m for each elbow or gate.
0006160034_201307
6
Suction pipe
7
Burner return pipe
8
Automatic fuel interception device at burner shut
off
9
Non-return valve
h metres
8
Automatic fuel interception device at burner
shut off
9
Non-return valve
10
Foot valve
h metres
1
Tank
h metres
3
Wire-net filter
4
pump
6
Suction pipe
7
Return pipe
10
Foot valve
11 / 30
L. Total Metres
Ø i. 14 mm.
1
30
1.5
35
2
35
2.5
40
3
40
L. Total Metres
Ø i. 14 mm.
1
30
1.5
35
2
35
2.5
40
3
40
Dimension p = 3.5 m (max)
L total metres
Ø i. 14 mm.
Ø i. 16 mm.
0.5
26
45
1
22
38
1.5
19
31
2
14
25
2.5
11
19

Werbung

loading