2.2.3. Connection of UV Lamp
• Unpack UV lamp and wipe it with a clean cloth (do not touch the lamp with your
fingers)
• Insert the lamp into the head piece until the transparent catching tabs of the
lamp connecting plug lock into place in the head piece (when you insert the lamp,
slightly press in catching tabs with two fingers; see figure 1 page 8)
• When inserting the UV lamp, make sure that the lamp filament wirings (see fig. 1
page 8) do not attenuate the sensor signal. The wirings must not be in front of
the sensor window.
3. Commissioning
Make sure to check all important items of the operating instructions
prior to commissioning.
3.1. Units with Solenoid Valve
• Loosen head piece by two turns
• Open stop valve of domestic water supply system
• Air escapes through the head piece. Leave the head piece open until water flows
out. After that relock the head piece. Be careful of splash water!
• Commission UV system. Insert plug into socket. The display shows: