Introduction
S CX27C EtherCAT® / PROFINET IRT, xCP-on-Ethernet and standard Eth­
ernet gateway
The module is used for connecting QuantumX modules and their signals to
any software via Ethernet or xCP-on-Ethernet. Connection to a fieldbus in
real time is also possible at the same time.
S MX878B Analog output module
The module has 8 scalable voltage outputs ("10 V) that can be assigned
with a system signal or a source signal. Signals can also be calculated in
real time.
S MX879B Multi‐I/O module
The module has 8 scalable voltage outputs and 32 configurable digital
inputs/outputs. Signals can also be calculated in real time.
All modules have the following in common:
S Supply voltage range 10 ... 30 V DC (nominal rated voltage 24 V DC)
S Configurable Ethernet interface for data communication with an operating
PC
S 2 IEEE1394b FireWire interfaces
- For optional voltage supply
- For optional data communication with a PC
- For automatic time synchronization of the modules
- For real-time transfer of measurement data between the modules
S Connector for installation on a backplane (not applicable for ultra-robust
variants)
S Status LEDs for displaying general system and channel states
S A factory calibration certificate is stored on each amplifier, which can be
read by the QuantumX Assistant.
S AutoBoot (module configurations are retained)
Each measurement channel features the following:
S Galvanic isolation (signal inputs/outputs, voltage supply, communication)
S Configurable supply voltage for active sensors
16