12
GROUP A -
1
SEN. 1
Analogue input configuration / sensor AI1 selection
tc. k
tc. s
tc. r
tc. J
Tc. T
tc. E
tc. N
tc. b
Pt100
ni100
ni120
ntc 1
ntc 2
ntc 3
Ptc
Pt500
Pt1k
rsvd.1
rsvd.2
0-1
0-5
0-10
0-20
4-20
0-60
Pot.
Table of Configuration
Parameters

- Analogue input 1

A. i n. 1
Sensor AI1
Tc-K
(Default)
Tc-S
Tc-R
Tc-J
Tc-T
Tc-E
Tc-N
Tc-B
Pt100
Ni100
Ni120
NTC 10K β3435K
NTC 10K β3694K
NTC 2252 β3976K -40° C..150° C
PTC 1K
Pt500
Pt1000
Reserved
Reserved
0..1 V
0..5 V
0..10 V
0..20 mA
4..20 mA
0..60 mV
Potentiometer (set the value on par. 6)
-260°
C..1360°
-40° C..1760° C
-40° C..1760° C
-200° C..1200° C
-260° C..400° C
-260° C..980° C
-260° C..1280° C
100° C..1820° C
-200° C..600° C
-60° C..180° C
-60° C..240° C
-40° C..125° C
-40° C..150° C
-50° C..150° C
-200° C..600° C
-200° C..600° C
User manual - ATR144 - 57