Cable entry
HSI90/HSI150
8 Installation: Preparing to install the sys-
tem cover/system seal
Observe before mounting the system cover:
• Complete removal of sealing pack sticker (pro-
tective film) prior to system cover installation
(see fig.: 15)!
• Carefully open the blind cover! Water pressure
possible inside the cable entry!
• Do not open the blind cover of the wall insert
until just before installing the cable. Observe
the installation instructions for the system co-
ver
• Any cable entries that are not required may be
used as pressure-tight back-up entries if there
is an undamaged Hauff quality seal on the clo-
sing cover.
• Do not knock the blind cover in with a ham-
mer or sharp object!
• Open cable entries, which are to be used as
back-up entries, or closing cover which have
been opened accidentally, should be fitted
with new HSI150 DT/DTS respectively HSI90 D
blind covers!
• Do not reuse uninstalled or damaged closing
covers!
1
Remove protective foil from the wall insert completely
(after warming slightly).
2
If necessary, clean out concrete residue from the
wrench threads on the black blind cover.
Use the SLS 6G(D) flexible socket wrench to open the
blind cover via the wrench threads by twisting to the
left (see fig.: 16).
3
With single wall inserts HSI150 with wall thickness 70
to 150 mm, the safety cover (second sealing cover)
on the connection side (bayonet mounting) is tapped
in with a hammer and removed. Optionally, the safety
cover can also be tapped in on the rear side.
Optional kann der Sicherheitsdeckel auch rückseitig
eingeschlagen werden.
The PE cover is then removed on the pipe side
(HSI150 K70 and K80 without PE cover) (see fig.: 17).
Further information on installing system
covers/system seals, see respective installation in-
structions.
Legend for fig.: 17
1
Safety cover (second seal)
2
Connection side (bayonet)
3
PE cover
Art. Nr.: 5090032067 Rev.: 05/2023-03-30

9 FHRK-Quality Seal

Tested products
Test report numbers
FHRK-Testing Specification
Service telephone + 49 7322 1333-0
EN
HSI150 YxZ K/X, HSI150
YxZ K2/X
G 30 322-3-10
21DE-01298
KD 101
Subject to change!