Set the starting current
Target cos 
Target displacement power factor.
4.3.2.3. T Probes commissioning
RVT can connect up to eight temperature probes in a daisy chain. Each probe needs to be commissioned as following
procedures before it can be used.
Each probe has to be recognized one by one:
– connect the probe to the temperature probe input (one probe only)
– click on a row to assign a probe number
– click on the "Start" button
– the RVT recognize automatically the probe address
– restart the same procedure for each probe
When one of the probes has a problem, it can be cleared by clicking the clear button.
A unique address will be assigned to each activated probe after the recognition completes.
– Connect each probe successively :
STATUS
Approved
Figure 45 Temperature probe auto recognition
SECURITY LEVEL
Public
PO WER FACTO R CON TR O LL ER RV T
DOCUMENT ID
9AKK107045A9645
REV.
LANG.
PAGE
D
en
59/542