Bit 14
Not used
Bit 15
Not used
5.5.2.9. Alarm Logging (GroupID = 0x0109)
Byte
Descrip-
Units
Offset
tion
0
Buffer 0
Alarm
Type
1
Time stamp
s
of alarm in
buffer 0
7
Buffer 1
Alarm
Type
8
Time stamp
s
of alarm in
buffer 1
14
Buffer 2
Alarm
Type
15
Time stamp
s
of alarm in
buffer 2
21
Buffer 3
Alarm
Type
22
Time stamp
s
of alarm in
buffer 3
28
Buffer 4
Alarm
Type
29
Time stamp
s
of alarm in
buffer 4
35
Buffer in-
dex
This table contains the alarm messages and the time stamp of their occurrences.
There is a circular buffer where both information are stored
– Kind of alarm logged.
– Time stamp.
This buffer may contain until 5 consecutive alarms.
A buffer index points to the eldest alarm logged.
When the buffer is full, the eldest alarm in the buffer is overwritten with the new one and the index is incremented.
The alarm type is defined as follows:
Value
Type
STATUS
Approved
RVT RVT3P Data
type
*
*
Byte
*
Time /
6
bytes
*
*
Byte
*
Time /
6
bytes
*
*
Byte
*
Time /
6
bytes
*
*
Byte
*
Time /
6
bytes
*
*
Byte
*
Time /
6
bytes
*
*
Byte
SECURITY LEVEL
Public
Size in
Default
bytes
value
1
0
6
0:0:0:0:0:0
1
0
6
0:0:0:0:0:0
1
0
6
0:0:0:0:0:0
1
0
6
0:0:0:0:0:0
1
0
6
0:0:0:0:0:0
1
0
Description
DOCUMENT ID
9AKK106713A9758
RVT CO MM UNI CATI O N
Min
Max
Modb @
value
value
0
9
42301
0:0:0:
255:12:3
42302
0:0:0
0:23:59:5
9
0
9
42305
0:0:0:
255:12:3
42306
0:0:0
0:23:59:5
9
0
9
42309
0:0:0:
255:12:3
42310
0:0:0
0:23:59:5
9
0
9
42313
0:0:0:
255:12:3
42314
0:0:0
0:23:59:5
9
0
9
42317
0:0:0:
255:12:3
42318
0:0:0
0:23:59:5
9
0
5
42321
REV.
LANG.
PAGE
K
en
39/71