4.3.1.4.4. Temp warnings
RVT provides 8 bank temperature warnings by eight temperature probes. Each temperature probe warning level can
be set independently. When any one of the eight temperature warning level is reached.
– the fan / warning relay will be activated: the NO contact will close
– the icon
is highlighted
Note 1: the RVT is self-protected against an internal over-temperature of 85°C. The actions described above will oc-
cur when the internal temp exceeds this protection level.
The RVT will restart automatically when the internal temperature falls back below 80°C.
Note 2: the temperature protection levels are disabled by default. When a level is entered, the RVT checks one of the
eight probe connections.
4.3.1.5. Restore default settings
Start screen Settings Manual settings restore default set.
STATUS
Approved
Figure 42 RVT temperature protection settings
Figure 43 RVT temperature warning settings