7 Unit settings menu
Ventilation
Ventilation time programme
Temperatures
Sensors
Fireplace
Brine EHE
Zone ventilation
3-way air shutter
Supplementary heating
EnOcean wireless
KNX
26
BACnet
Switching test
Internet
NOTICE: Incorrect settings can cause faults and
malfunctions. Settings can only be undertaken in
the installer level by authorized trained specialists
in ventilation technology. To activate the installer
level, go to "Installer" field and enter the pass-
word 6940.
7.1.1 Basic settings
Single control unit lock
Room sensor configuration
Single control unit: RB-ZF4 control panel
Single control unit: Blocking off
Switching contact function
Bypass
Heat register configuration
Heat exchanger type
Acknowledgement of external safety device
Factory settings for control
7.1.1.1 RB-ZF4 control panel locking
Control panels can be locked from a main control
unit. All single control panels are then deactiv-
ated.
Parameters: Control panel locking
Setting value:
Inactive: All control panels unlocked.
Active: All control panels deactivated.
7.1.1.2 Room sensor configuration
Parameters: Room sensor configuration
Setting value: Internal, Bus
The temperature determined with the selected
room sensor is used as the room temperature to
control the bypass and any supplementary heat-
ing connected.