4

Commissioning

First make all electrical connections and then carry out the
commissioning!
▶ Observe the installation instructions for all components and
assemblies in the system.
▶ Only switch on the power supply after all modules are set up.
4.1

Setting the coding switch

When the coding switch is in a valid position and communication is
established via the BUS system, the status indicator lights up green
continuously. When the coding switch is in an invalid or intermediate
position, the status indicator initially does not light up then lights up red.
4.2

Commissioning of the system and module

1. Isolate all poles of the mains voltage and secure against
reconnection.
2. Make sure the mains voltage is disconnected.
3. Connect all required sensors and actuators.
4. Mechanically establish the power supply (230 V AC) at all installed
modules and heat sources.
5. Set the coding switch at the module.
6. Set the coding switch at other modules, if necessary.
7. Switch on the power supply (mains voltage) to the entire system.
Once the status indicator on the module lights up green constantly:
8. Start commissioning the control unit  installation instructions of
control unit.
9. In the service menu Commissioning > Start configuration
wizard? > Yes set Altern. HS and follow up to menu. The
configuration wizard suggests a configuration for the ME 200 based
on the connected sensor.
10.Check the settings in the menu ME 200 ( Table 8 to 12) and adjust
to the installed system if required.
Step 9 and 10 are important otherwise a fault may occur on the C 400/
C 800 which will lead to misinterpretations.
11.Make remaining adjustments as described in the installation
instructions for the control unit.
4.3

More status indicators at the module

In addition to the coding switch, the module has 4 LEDs that indicate the
status of each of the connected nodes  Tab. 13.
4.4

Settings menu of alternative heat source

If a ME 200 is installed, the Service menu > Set altern. HS menu is
displayed at the user interface (setting of alternative heat source).
The following overview provides a brief description of the Set altern. HS
menu. The menus and settings available in these menus are described in
detail on the following pages.
Menu overview Set altern. HS
• Alt. heat source activation – for active activation of the alternative
heat source
• Relay output config. – use of connecting terminal VR2
• Buffer primary pump – settings of primary pump
• Mixer return AHS – mixer settings for return temperature increase of
alternative heat source
• Buffer – settings for buffer cylinder charging
• Blocking mode – conventional heat source interlock functions
ME 200 – 6721841615 (2021/11)
The factory settings are shown in bold in the setting areas.
CAUTION
Risk of scalding due to omission of temperature limit.
If the only heating circuit is a heating circuit without mixer, this can result
in high temperatures.
▶ Installing the temperature limiter.
NOTICE
Damage to device due to cold water in the heat source!
▶ Observe the manufacturer's specifications in relation to the minimum
return temperature of alternative heat source.
▶ Set the temperature for return temperature increase of the
alternative heat source according to the manufacturer's
specifications.
Meu item
Setting area: function description
Altern. HS installed
Appears only with coding switch setting 1.
• Yes: ME 200 in the system, even if ME 200 does not
control any alternative heat source.
• No: no ME 200 in the system. Bis ME 200 version
NF03.02 (before 11/2021) without function.
Alt. heat source
Yes: active alternative heat source. The module
activation
switches the alternative heat source on, depending on
demand (switching contact required on alternative heat
source).
The alternative heat source can be modulated as an
option (0-10 V output-regulated interface required at
alternative heat source).
No: none or passive alternative heat source. No active
activation of the alternative heat source (e.g. (wood-
burning) stove).
Relay output config.
Off: no connection at VR2
1)
(VR2)
HC1 PM: pump for heating circuit 1 connected to VR2
can only be used for stand-alone alternative heat source
(coding switch setting 10).
1) can only be set with ME 200 addr. 10
Table 8 Menu Commissioning / Altern. HS
The minimum output power of the alternative heat source is set fixed at
35 %.
Commissioning
37