Verfügbare Sprachen

Dry contact interface
B.
 Function:
The dry contact interface can turn on/off the generator and is connected parallel with the
generator's switch.
Working principle:
When the battery voltage reaches the dry contact ON voltage (DON), the dry contact is
connected. Its coil is energized. The dry contact can drive loads of no more than 125VAC
/1A, 30VDC/1A. According to different battery types of the inverter charger, the default
values of the dry contact ON(DON) voltage and the dry contact OFF (DOF) voltage are
different. Please refer to the chapter 3.5 Settings > item 19 DON and item 20 DOF for
details.
Connect the RTS interface
C.
Category
Included accessory
Optional accessory
Suppose the remote temperature sensor is not connected to the controller. The default
setting for battery charging or discharging temperature is 25 °C without temperature
CAUTION
compensation.
www.solarv.de
Name
External temperature sensor
Remote Temperature Sensor
19
Model
RT-MF58R47K3.81A
RTS300R47K3.81A
Copyright © 2021 SolarV GmbH All rights reserved