Connect the battery
3)
A circuit breaker must be installed on the battery side. For selection, please refer to
chapter
WARNING
 When wiring the battery, please do not close the circuit breaker and ensure that
 A circuit breaker current is 1.25 to 2 times the rated current must be installed on
CAUTION
Connection sequence of the battery
Step1: Remove the screw of the inverter/charger positive terminal with a sleeve, the
torque of which is 3.5N.M.
Step2: Connect the ring terminal of the battery connection wire to the inverter/charger's
positive terminal.
Step3: Install the screw and secure it with the sleeve.
Step4: Connect and secure the negative terminal of the inverter/charger following the
step1~step3.
Connect the AC load
4)
 Risk of electric shock! When wiring the AC load, please do not close the circuit
 If utility input exists, the inverter/charger must be connected to the ground
WARNING
www.solarv.de
"2.2.2 Prepare modules
the leads of "+" and "-" poles are connected correctly.
the battery side away from the battery not longer than 200mm.
breaker and ensure that the poles leads are connected correctly.
terminal.
".
16
Copyright © 2021 SolarV GmbH All rights reserved