UP3000-HM5041
UP3000-HM5042
UP3000-HM8041
UP3000-HM10021
UP3000-HM10022
UP5000-HM8042
Making the battery connection wire
Step1: Ring terminal 2pcs (included accessories).
Step2: Battery positive and negative connection wires 2 pcs (red +, black -). The wire
length is determined according to the customer's actual requirement.
Step3: Strip one end of the battery connection wire for about d mm (size d is determined
according to the ring terminal).
Step4: Pass the exposed wire through the ring terminal and secure the wire firmly with a wire
clamp.
AC Load
2)
Recommended wire size of the AC load and the circuit breaker is as below.
Model
UP2000-HM6021
UP2000-HM6022
UP3000-HM5041
UP3000-HM5042
UP3000-HM8041
UP3000-HM10021
UP3000-HM10022
UP5000-HM8042
Making the connection wire of the AC load:
Strip the AC load connection wires (3 pcs) for about 10 mm.
Symbols
L
N
PV modules
3)
Recommended wire size of the PV module and the circuit breaker is as below.
www.solarv.de
2
16mm
/5AWG
2
16mm
/5AWG
2
16mm
/5AWG
2
35mm
/1AWG
2
35mm
/1AWG
2
35mm
/1AWG
Load wire size
2
6mm
/9AWG
2
3.4mm
/12AWG
2
6mm
/9AWG
2
4mm
/11AWG
2
6mm
/9AWG
2
6mm
/9AWG
2
4mm
/11AWG
2
6mm
/9AWG
Abbreviation
LINE
Neutral
—
11
2P—100A
2P—100A
2P—100A
2P—200A
2P—200A
2P—200A
Circuit breaker
2P—40A
2P—16A
2P—40A
2P—25A
2P—40A
2P—40A
2P—25A
2P—40A
Name
Live wire
Neutral line
Ground line
Yellowish green
Copyright © 2021 SolarV GmbH All rights reserved
EN
RNB22-8
RNB22-8
RNB22-8
RNB38-8S
RNB38-8S
RNB38-8S
Torque
1.2N.M
1.2N.M
1.2N.M
1.2N.M
1.2N.M
1.2N.M
1.2N.M
1.2N.M
Color
Brown/black
Blue