Magnetostrictive Linear Position Sensor – Rod Style
9
Adjust with the calibration device (continued)
Switch the output to be adjusted (optional)
As standard, the values are adjusted at output 1
and the values at output 2 are inverted
accordingly.
The adjustment can be switched from output 1
to output 2.
Initial situation:
BTL with magnet in measuring range
Activate adjusting
► Hold down
‚ ‚
for at least 4 s.
Switch the output to be adjusted
Œ Œ
‚ ‚
► Hold down
and
⇒ The output changes with each switch.
► Continue with Set start point (see page 22).
1
= blue button
= gray button
2
24
english
for at least 4 s.
Type of protection "db" and "t"
2
> 4 s
1
2
> 4 s
Flameproof enclosure
Displayed values (example)
At 0...10 V
At 4...20 mA
5.39 V
9.15 mA
5.39 V
9.15 mA