BTL7-A/E501-M_ _ _ _-J-DEXC-TA12
Magnetostrictive Linear Position Sensor – Rod Style
7
Adjust with the calibration device (continued)
7.3.2

Adjust

The detailed procedure for adjusting is
described on page 22 ff.
The factory-set null point and end point are replaced by a
new start point and end point and the associated output
values can be adjusted. The start and end values can be
adjusted as you like up to the limits. The change to the
output value can be read out at output 1 (in the delivery
state).
As standard, the values are adjusted at output 1
and the values at output 2 are inverted
accordingly.
The adjustment can be switched from output 1
to output 2 (see page 24).
Steps
► Move magnet to the new start position.
► Read new start point by pressing the buttons.
► Set the new start value by pressing the buttons.
New start
value
Start point
Fig. 7-3:
Adjust a new start value
20
english
► Move magnet to the new end position.
► Read new end point by pressing the buttons.
► Set the new end value by pressing the buttons.
New end value
Before
After
Fig. 7-4:
Adjust a new end value
7.3.3

Reset

The detailed procedure for the reset is
described on page 25.
Restoring the BTL to its factory settings.
Before
After
Type of protection "db" and "t"
Flameproof enclosure
End point