5. Commissioning, operation
The characters within one message may not have spacing of more than 1.5 characters.
Examples of a typical transmission:
Intermission Message 1
EN
Valid function calls
Function Designation
03
Read holding registers
04
Read input register
06
Write single register
16
Write multiple registers
08
Diagnostic -
Sub code 00
23
Read/write multiple
registers configuration
5.6.2.5 Data register, measured values
Measured values can only be read and not written.
Model GD-20
Register
Measurand
00000
Pressure (abs.)
00002
Pressure (abs.)
00004
Pressure
00006
Pressure
00008
Pressure
00010
Pressure
00012
Temperature
00014
Temperature
00016
Temperature
00018
Gas density
00020
Gas density
00022
Pressure standard-
ised to 20 °C [68 °F]
00058
Pressure standard-
ised to 20 °C [68 °F]
26
Intermission Message 2
Description
Reading of one/more register values or the instrument
configuration
Reading a register value or the instrument configuration
Writing a register value or the instrument configuration
Writing of one/more register values or the instrument
configuration
Diagnostic function
Writing or reading of one/several register values or the
instrument configuration
Unit
p
bar
p
MPa
p
Pa
p
kPa
p
psi
p
N/cm²
T
°C
T
K
T
°F
rho
g/l
rho
kg/m³
p20
bar
p20
bar (gauge
pressure)
WIKA operating instructions, model GDM-RC-100-T
Intermission Message 3 ...
Based on
Absolute pressure
Absolute pressure
Absolute pressure
Absolute pressure
Absolute pressure
Absolute pressure
Absolute pressure at 20 °C [68 °F]
Gauge pressure at 20 °C [68 °F]
based on 1,013 mbar