Status Register - WIKA GDM-RC-100-T Betriebsanleitung

Hybrid-gasdichtewächter mit referenzkammer
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5. Commissioning, operation
Parity
Parity
Register value
None
0 (standard)
1
Even
TAG number
Here, a transmitter name with up to 16 characters can be entered.

5.6.2.7 Status register

Register Function
00200
Error memory
00201
Error memory reset
00202
Software reset
00203
Resetting to standard
After a restart (voltage supply was interrupted), the error memory is reset. Writing 0x0001 in
register address 00201 has the same effect.
Description of the error memory
Bit
Description
1
Pressure signal above the upper limit value (in bar abs., →see data sheet SP 60.77)
3
Temperature signal below the lower limit value (< -40 °C [-40 °F])
4
Temperature signal above the upper limit value (> 80 °C [176 °F])
5
Communication error pressure/ temperature sensor
6
Liquefaction of the SF
7
Gas density above the upper limit value (based on the full scale of the density measuring
range in bar abs. at 20 °C [68 °F])
10
Recurring Modbus
Example: 0x0082
Bit 1 and 7 are set. The upper limit values for pressure and gas density are exceeded.
Software reset
Writing 0x0001 in register 202 causes a software reset. After this process all changed
parameters take effect (e.g. change of address).
Reset to factory settings
Writing 0x0001 in register 203 causes the transmitter to be reset to its factory settings
and a software reset to be carried out. After this process, all writable registers are reset
to the initial setting.
WIKA operating instructions, model GDM-RC-100-T
Value definition, triggering the
function
16 bit (see the following table)
Writing 0x0001
Writing 0x0001
Writing 0x0001
gas
6
communication error
®
EN
Writable
Read only
Yes
Yes
Yes